For most of the last two decades, data centre cooling meant moving cold air. Raised floors, containment aisles and CRAH units were refined year after year, and for racks drawing a few kilowatts each, that worked well.
AI and high-performance computing have changed maths. GPU racks now draw several times the power of a typical enterprise rack, and air simply cannot carry that much heat away from such a small footprint without enormous fan power and very cold supply air. That is why liquid cooling for data centres has moved from niche to mainstream planning, especially in Singapore, where operators also face some of the tightest efficiency expectations in the region.
This article explains where air cooling reaches its limits, the main types of liquid cooling, and what our engineers look at when a facility is deciding whether, and how, to make the move.
Why Air Cooling Hits a Limit
Air is a poor carrier of heat compared with water. To remove more heat with air, you either move more of it or make it colder, and both cost energy. As rack density rises, three problems appear together:
- Fan power climbs steeply. Moving enough air through a dense rack takes far more fan energy, which shows up directly in your PUE (power usage effectiveness, the ratio of total facility power to IT power).
- Hot spots become harder to control. Even with containment, high-density racks create local recirculation that can starve the top of a rack or the end of a row of cold air.
- Chilled water temperatures have to drop. Colder supply air means colder chilled water, which reduces chiller efficiency and the number of hours you can use free or economised cooling.
There is no single cut-off point, but as a working rule, many operators start finding air cooling difficult somewhere in the range of 30 to 40 kW per rack. Current AI training racks are widely reported to exceed 100 kW. At that level, liquid cooling is no longer an efficiency upgrade. It is the only practical option.
Posted on Google![]()
Jack YeeTrustindex verifies that the original source of the review is Google.
Good support and fast response. Highly recommended.
Owner's reply
Thank you, Jack, for the kind words. We are glad our team could support you quickly, and we truly appreciate you taking the time to share your experience. Looking forward to working with you again.Posted on Google![]()
Kenny sikTrustindex verifies that the original source of the review is Google.
A simulator with reliable, good support and reasonable fees. Able to understand your requirements without lengthy brief. Recommended to engage them.
Owner's reply
Thank you, Kenny, for your kind review and recommendation. We truly appreciate your trust in Megagenix and are glad that you found our support responsive, reliable and straightforward. It has been a pleasure working with you, and we look forward to supporting you again on future projects.Posted on Google![]()
William GohTrustindex verifies that the original source of the review is Google.
They demonstrated strong technical expertise in CFD analysis and provided clear, well-structured reports that were easy to understand. Highly recommend their CFD consulting services to anyone looking for accurate simulations, professional support, and dependable engineering expertise.
Owner's reply
Thank you very much for your kind review and recommendation. We are pleased to know that you found our CFD analysis technically strong and our reports clear and easy to understand. It was a pleasure supporting your project, and we look forward to working with you again in the future. ❤️Posted on Google![]()
CHOONG XING YUNGTrustindex verifies that the original source of the review is Google.
The team is always opened to discussion even the timeline is tight and they are still able to commit to help us earlier than the deadline. They also provide advice on the design even though they ought to do the simulation only. Very helpful and efficient team, highly recommended 👍
Owner's reply
Thank you Mr Choong for your kind words and recommendation. We truly appreciate your trust in our team. We understand the project timelines can often be challenging, and we always do our best to support our clients by responding promptly while maintaining the quality of our work. At Megagenix, we believe our role is not only to provide simulation results, but also to help clients make informed engineering decisions. We look forward to working with you again on future projects.❤️Posted on Google![]()
Wen HongTrustindex verifies that the original source of the review is Google.
Good
Owner's reply
Thank you, Wen Hong, for your 5-star review! We truly appreciate your support and are glad you had a positive experience with Megagenix.Posted on Google![]()
soon tcTrustindex verifies that the original source of the review is Google.
Megagenix was responsive throughout the project we have engaged with them, quickly addressing our requests and keeping communication clear. Their CFD analyses were well presented and easy to understand, and their support with design changes helped us make decisions more efficiently.
Owner's reply
Thank you very much for your kind feedback and for giving Megagenix the opportunity to support your project. We are pleased to know that our responsiveness, clear communication and CFD analysis helped your team evaluate the design changes and make decisions more efficiently. We truly appreciate your trust and look forward to supporting you again in future projects.Posted on Google![]()
Jason LeeTrustindex verifies that the original source of the review is Google.
I've been working with Megagenix since last year on several data center CFD simulation projects. Their team has been professional, responsive and provided valuable recommendations from the design stage, particularly on airflow optimisation. I especially appreciate their strong commitment and support in overcoming challenges throughout both the pre- and post-simulation phases while helping us meet tight project timelines. I highly recommend Megagenix for anyone looking for reliable and professional CFD simulation support.
Owner's reply
Hi Jason, Thank you very much for your kind and thoughtful review. We truly appreciate your continued trust in Megagenix and the opportunity to support you across several data centre CFD projects. It has been a pleasure working with you and your team to overcome project challenges and meet the project timelines. Your feedback is greatly appreciated and motivates our team to continue delivering responsive and reliable technical support. We look forward to continuing our collaboration and supporting your future projects. ❤️Posted on Google![]()
ColdTec AdminTrustindex verifies that the original source of the review is Google.
I have approached Megagenix with a very urgent project and an extremely tight timeline. Their team demonstrated great professionalism and responded quickly, helping us complete the Heat Load Calculation and CFD report on time for our submission. I'm very satisfied with their service and technical expertise. Thank you, Megagenix, for your excellent support—I look forward to working with the team again on future projects.
Owner's reply
Thank you, ColdTec team, for your kind review and trust in Megagenix. We are pleased that our team was able to support your urgent Heat Load Calculation and CFD analysis within the required timeline. We truly appreciate your recognition of our responsiveness, professionalism, and technical expertise. We look forward to supporting ColdTec again on future engineering projects.❤️Posted on Google![]()
Rentatt HengTrustindex verifies that the original source of the review is Google.
As a representative of DCD Technology Sdn. Bhd., we had a positive experience working with Megagenix. Their team was responsive, technically knowledgeable, and provided practical engineering support throughout the project. They took the time to understand our requirements, communicated clearly, and addressed our questions promptly and professionally. We appreciate their commitment to delivering quality engineering solutions and would recommend Megagenix to anyone seeking reliable CFD simulation and engineering consulting services.
Owner's reply
Thank you, Mr. Rentatt for taking the time to share your experience and for your kind recommendation. We truly appreciate the opportunity to support DCD. Your trust means a lot to us, and we are glad that our team could provide responsive and practical engineering support throughout the project. We look forward to collaborating with you again on future CFD and engineering simulation projects. ❤️Posted on Google![]()
Amy WongTrustindex verifies that the original source of the review is Google.
Used Megagenix for a recent project. What I appreciated is that they look at the simulations through a practical lens. Instead of just highlighting where the flow was failing in the software, they sat down with us and suggested realistic layout tweaks to fix the hot spots. Catching those blind spots early saved us a ton in potential modification costs down the line. Solid, pragmatic engineering team
Owner's reply
Thank you, Amy, for your wonderful feedback. We are pleased that our team was able to provide practical recommendatkons that helped your team to address the hot spots early and potentially reduce downstream modification costs. At Megagenix, we strive to bridge the gap between simulation results and real-world engineering solutions. We really appreciate your trust and look forward to supporting your future projects.😊Load moreVerified by TrustindexTrustindex verified badge is the Universal Symbol of Trust. Only the greatest companies can get the verified badge who has a review score above 4.5, based on customer reviews over the past 12 months. Read more
The Singapore Context
Singapore adds two pressures that make the decision more urgent.
First, the climate. High temperatures and humidity all year round limit the free cooling hours that data centres in temperate countries rely on. Every efficiency gain has to come from the cooling design itself.
Second, policy. IMDA’s Green Data Centre Roadmap sets out to bring all data centres in Singapore to a PUE of 1.3 or better at 100% IT load over the next ten years. The roadmap also committed to introducing standards for IT equipment energy efficiency and liquid cooling. New capacity awarded under the second Data Centre Call for Application (DC-CFA2) has been held to a stricter PUE requirement still. For operators planning AI capacity, liquid cooling is increasingly part of how those targets get met. (Our PUE optimisation page explains how we model a facility against these targets.)
The Main Types of Liquid Cooling
Rear-Door Heat Exchangers
A water-cooled coil replaces the rear door of the rack, so hot exhaust air is cooled as it leaves the rack. The servers themselves are unchanged and still air-cooled.
Best for: retrofitting existing halls with moderately dense racks, without changing IT hardware. It extends the life of an air-cooled hall rather than replacing it.
Direct-to-Chip (Cold Plate) Cooling
Liquid flows through cold plates mounted directly on the processors and GPUs, carrying away most of the heat at the source. A coolant distribution unit (CDU) connects the rack loop to the facility water system. The remaining heat from memory, power supplies and other components is still removed by air.
Best for: high-density AI and HPC racks. This is the approach most new GPU platforms are designed around.

Immersion Cooling
Servers are submerged in a non-conductive fluid that absorbs heat from every component. In single-phase systems the fluid stays liquid and is pumped through a heat exchanger. In two-phase systems it boils off the components and condenses again.
Best for: very high densities and specialised deployments. It removes nearly all server fans, but it changes how hardware is serviced and needs compatible equipment.
| Rear-door heat exchanger | Direct-to-chip | Immersion | |
|---|---|---|---|
| Changes to IT hardware | None | Cold plates on chips | Hardware rated for immersion |
| Heat still removed by air | All of it, at the rack door | A minority share | Almost none |
| Typical use | Retrofit, moderate density | New AI and HPC deployments | Highest densities, specialised sites |
| Main design challenge | Water at the rack, coil capacity | CDU sizing, residual air load | Serviceability, fluid handling |
Why Most Facilities End Up With a Hybrid Hall
In practice, very few halls go fully liquid overnight. A typical scenario is a hall that keeps its existing air-cooled racks while adding rows of direct-to-chip GPU racks. That hybrid setup is where many projects run into trouble, because:
- Direct-to-chip racks still reject a share of their heat to air, and that share is easy to underestimate when the rack’s total power is very high.
- The air system was sized for the old layout. New high-density rows can disturb airflow to neighbouring air-cooled racks.
- The facility water loop now serves two very different loads, often at different supply temperatures.
This is where simulation earns its keep. Using data centre CFD (computational fluid dynamics, a way of modelling airflow and heat in 3D), we model the residual air load from liquid-cooled racks alongside the existing air-cooled ones, and check that every rack still receives air at the right temperature. You can see an example in our hybrid cooling CFD case study.

Questions to Answer Before You Commit
- What will the rack densities actually be, and when? Plan for the hardware roadmap, not just the first deployment.
- How much heat will still go to air? This decides whether your existing CRAH units and containment can cope.
- What water temperatures can the system run at? Warmer water for liquid-cooled loops can improve chiller efficiency and increase economiser hours, but only if the rest of the plant is designed for it.
- How does the change affect annual PUE, not just peak? A design that looks good at full load can underperform at partial load. Hourly, whole-facility modelling shows the real annual picture.
- What happens if a CDU or pump fails? Liquid-cooled racks heat up much faster than air-cooled ones when cooling stops, so redundancy and response times need to be modelled.
How Megagenix Helps (Liquid Cooling For Data Centres)
We are an independent engineering consultancy. We don’t sell or install cooling equipment, so our recommendations are vendor-agnostic. For liquid and hybrid cooling projects, our engineers:
- model the hall with CFD to check air-side performance around new liquid-cooled racks;
- size liquid and hybrid cooling systems against your planned rack densities;
- run whole-facility energy simulation to show the effect on annual PUE;
- test failure scenarios before they happen in a live hall.
If you’re planning AI capacity or a hybrid retrofit, speak to our engineers before the cooling design is fixed. It’s far cheaper to change a model than a live hall.
Frequently Asked Questions
At what rack density do you need liquid cooling?
There is no fixed threshold, but many operators find air cooling becomes difficult and inefficient somewhere around 30 to 40 kW per rack. Current AI training racks can go well beyond 100 kW, where liquid cooling is effectively required.
What is the difference between direct-to-chip and immersion cooling?
Direct-to-chip cooling pumps liquid through cold plates attached to the main processors, while the rest of the server is still air-cooled. Immersion cooling submerges the whole server in a non-conductive fluid that absorbs heat from every component.
Can an existing air-cooled data centre add liquid cooling?
Yes. Rear-door heat exchangers can be added with no change to servers, and direct-to-chip racks can be introduced alongside air-cooled ones. The air system and facility water loop need to be checked for the new mix of loads, which is best done with CFD and energy modelling before installation.
Does liquid cooling improve PUE?
It usually does, because it reduces fan energy and can allow warmer water temperatures that improve chiller efficiency. The actual improvement depends on the whole plant design, so it should be modelled on an annual, hourly basis rather than assumed.